Grenkago ENFRAR
Home / Error Code Reference

Solar Inverter Error Codes & Alarm Reference

One line: Faults and alarms behave differently — read the indicator first, then the code. Some codes clear on their own; three do not, and those need the manufacturer.
Front panel of an inverter with the LCD showing status information
The LCD shows the code; the indicator tells you whether it is a fault (shutdown) or an alarm (still running).

Fault vs alarm — read the indicator first

TypeIndicatorBuzzerSystem actionRecovery
Alarm (warning)Alarm/fault light flashesSounds once per second for 1 minuteThen stopsClears when the condition ends
FaultFault light stays lit, LED red solid, code on LCDSounds for 10 seconds, then stopsSystem attempts restart; after six attempts it stays in faultRequires full power removal or a 30-minute wait
Fault lockCode on LCD—A recoverable fault can restart 6 times within 15 minutesBeyond six attempts the lock triggers; clears after 15 minutes

The first action in any troubleshooting sequence is to note which light is doing what. A flashing light is an alarm — usually a condition the system can ride out. A solid light is a fault — the unit has stopped and wants intervention.

Fault codes

CodeMeaningTriggerRecoverable
1Bus soft-start failureBus voltage did not reach the set valueYes
2Bus over-voltageBus voltage above the protection pointYes
3Bus under-voltageBus voltage below the protection pointYes
4Battery over-currentCurrent interrupt triggered twice or more within 2 msNo
5Over-temperatureTemperature above threshold, or fan blockedYes
6Battery over-voltageBattery voltage above the set valueYes
7Bus soft-start faultSoft-start window passed but bus voltage did not reach the set valueYes
8Bus short circuitBus voltage below the critical value when inverter or PFC engagedYes
9Inverter soft-start faultRated output voltage not reached after soft-startYes
10Inverter over-voltageInverter voltage above the set valueYes
11Inverter under-voltageInverter voltage below the set value in battery modeYes
12Inverter short circuitCurrent above the set value at low inverter voltage, in battery or standby modeYes
13Negative power protectionLoad power below the set value in battery mode (e.g. −1200 W)Yes
14Overload faultOverload beyond the defined limitYes
15Model faultModel detection matches no known model—
16No start-up programThird digit of the communication value incorrect—
26BMS faultError code in the BMS messageYes (disable BMS comms or clear the BMS fault)
27MCU faultMCU errorNo
29Inverter time-zone faultTen or more fast over-current events in each of four consecutive half-cyclesYes

Alarm codes

CodeMeaningActionTriggerRecovery
50Battery open circuit / not connectedAlarm, battery not chargingBattery below 8 V (HE200-2500-O); or not detected within 10 minutes (HE200-6500-T / 7200-F)Battery above 10 V; or charge for 2 minutes after connecting
51Battery under-voltage shutdownAlarm, battery low-voltage shutdown or failure to startBattery voltage below the set valueRecovers when battery voltage is restored
52Battery low voltageAlarmBattery voltage below the set valueRecovers when battery exceeds the set value by 2 V
53Charger short-circuit warning, battery not chargingAlarmHE200-6500-T: individual cell below 6 V with charge current. HE200-7200-F: battery below 20 V with charge current above 4 ANo
56BMS lostAlarmBMS communication failed with the function enabledComms disabled, or connection restored
58Fan faultAlarm, fans run at full speedAny fan making fewer than 10 rotations in 5 seconds (HE200-3000-O-I5); or no fan speed signal detected (HE200-6500-T / 7200-F)Recovers when a fan speed signal is detected
59EEPROM faultAlarmEEPROM read/write abnormalityRecoverable by restoring factory defaults
60OverloadAlarmSupply current, discharge current or load power above rating (HE200-6500-T); output current above 40 A (HE200-7200-F)HE200-6500-T: when all three fall below rating. HE200-7200-F: when output current drops below 38 A
62PV energy onAlarm; stops PV output to the load, keeps PV charging the batteryBus voltage below the set value with no battery connectedBattery or utility connected
Code 34 appears in some HE200-6500-T / HE200-7200-F manuals without a defined meaning. We note it as undefined rather than guess.

Troubleshooting quick reference

SymptomConditionAction
Code 5 — over-temperatureFan locked for over 10 secondsCheck the fan is connected and the wiring is secure. If it is disconnected for over 10 seconds the unit reports code 5.
Code 12 — inverter short circuitBelow 80 V inverter voltage with over 5 A inverter current, response within 80–100 ms① Check the output terminals for a short — a screw piercing a terminal can short L and N. ② Verify the inverter voltage and current conditions.
Code 15 — model faultModel detection matches nothingCheck the control board is assembled correctly and the correct firmware is flashed.
Code 16 — no start-up programCommunication third digit incorrectSend command TIDA1911000000000000.
Code 58 — fan faultFewer than 10 rotations in 5 seconds① Check the fan connection. ② If correct, check the detection circuit (excess solder under the control-board socket is a common cause), then check for a failed fan.
Will not start — batteryBattery mode needs ≥11.5 V per cell① Check battery voltage sampling and calibration. ② Measure at the battery terminals with a multimeter and confirm the minimum per-cell voltage. ③ Check item 46 in the parameter list for BSU configuration. Configuring the wrong battery voltage for the model can cause the capacitor to burst.
Will not start — utility—① Check the supply terminals for a short — a screw through the housing can short live and neutral. ② Check for wiring errors, such as the supply input connected to the output terminal.
Will not start — PV—Check whether the PV input voltage is too close to the threshold.
PV not charging—Connecting the wrong battery voltage can damage the PV-side auxiliary supply, causing power loss and loss of communication with the main controller.

Standard troubleshooting sequence

  1. Isolate. Disconnect the inverter from all external power sources and wait at least 5 minutes before working on it.
  2. Read the code. Note the code on the LCD.
  3. Classify. Solid light → fault table. Flashing light → alarm table.
  4. Check the trigger condition. Compare voltage, current and temperature readings against the trigger band for that code.
  5. For recoverable faults. Try full power removal or a 30-minute wait.
  6. For non-recoverable faults. Codes 4, 27 and 53 require the manufacturer.
  7. Fault lock. Six restarts in 15 minutes locks the unit; wait 15 minutes.
  8. Board or firmware issues. Codes 15 and 16 need factory intervention.
Rear plate of an inverter showing the ventilation grille
Before chasing a code, confirm airflow and that the rating label matches the model you are servicing.

Fault codes by series — what this page covers

Not every series in our range publishes the same code set, so coverage is stated model by model rather than assumed:

SeriesCode table statusOn this page
HE200 — 2500-O, 3000-O-I5, 6500-T, 7200-FComplete fault and alarm tablesFault codes 1–29, alarm codes 50–62
HE300 — 4200-T, 7200-F, 12000-F, parallel modelsDiffers from HE200 in placesNot tabulated here
HE310-5000-FNo published fault tableNot covered
L2 / H3 / H4 all-in-oneNo fault-code chapter in the documentationNot covered

This reference is compiled from the four HE200 manuals. The HE300 alarm and fault set is not identical — for example the HE300-4200-T raises a message tied to maximum utility charge current, which has no HE200 equivalent. We would rather leave that gap visible than publish a code table we cannot source.

For an HE300 code not listed here, send us the model, the code on the LCD and the indicator state — solid light or flashing — and we will match it against the manual for that unit.

Always follow the manual shipped with the unit. Where this page and the manual disagree, the manual governs.

Code 13 and code 59 in detail

Two codes account for a disproportionate share of the questions we receive, so they are expanded here.

Code 13 — negative power protection. In battery mode the unit measures load power; code 13 appears when that measurement is negative, meaning power is flowing into the inverter from the output side instead of out to the load. The manual defines the threshold (for example −1200 W) but does not prescribe a field remedy. In practice, look for a second AC source landing on the output side — a generator, another inverter, or a back-fed utility circuit — and confirm the measurement wiring direction.

Code 59 — EEPROM fault. An EEPROM read or write abnormality. It is recoverable by restoring factory defaults. If it returns after a defaults restore, treat it as a board-level issue rather than a settings problem and contact us before replacing parts.

Related pages

Ask our technical team