One line: Pumps are the hardest load in solar. The running watts are small; the starting surge is not. Get the surge margin wrong and the system trips every time the pump starts.
Portable all-in-one energy storage unit, front three-quarter view showing the connection panel and outlets
Pumps are a special case: starting current can be several times the running current.

Why pumps are a special case

An irrigation pump's nameplate might read 1.5 kW. At start-up, before the motor reaches speed, it can draw 3 to 4.5 kW for a fraction of a second — and this happens every time the pressure switch or timer cycles the pump on.

High-frequency inverters have limited surge tolerance. A unit rated just above the running load will trip on start, alarm, restart, trip again — and the farmer concludes the inverter is faulty when the specification was wrong.

Two solutions:

  1. Size the inverter well above the running load — typically 2–3× the largest motor, so surge sits inside the rating.
  2. Choose a low-frequency unit, which steps through a large transformer and tolerates surge far better.

When low-frequency is the answer

The HE310-5000-F is built for exactly this class of load:

ParameterValueWhy it matters
Rated power5000 W / 6300 VAThe VA rating gives headroom for poor power factor
Load peak ratio3:1A 1.5 kW pump with a 4.5 kW surge sits inside the capability
Battery voltage48 VDCHigh current capability for motor starting
Battery capacityUp to 500 AhSustained draw for long pump runs
Input voltage range154–264 VACTolerates weak or unstable rural supply
No-load lossBelow half a same-power high-frequency unitMatters on long idle periods
Noise<45 dB—
Efficiency>98%—

The 3:1 peak ratio is the specification that matters. It is the difference between a system that starts the pump and one that does not.

When a hybrid unit is enough

For a small, intermittently-used pump — a transfer pump for topping up a tank, say — a high-frequency hybrid unit with generous headroom does the job at lower cost:

Pump running loadSuggested hybrid model
Up to 750 WHE200-3000-O-I5 — 2000 W, IP54
0.75–1.5 kWHE200-4200-T — 3600 W, 24 V
1.5–3 kWHE200-7200-F — 6200 W, 48 V
3–5 kW, or repeated hard startsHE310-5000-F — low-frequency, 3:1 peak

The dividing line is not the running load but the number and hardness of starts. A pump that starts twice a day on a light duty cycle tolerates a high-frequency unit. A pump that starts on a pressure switch every few minutes does not.

Sizing the array for water pumping

Pumping is energy-intensive, and irrigation demand often peaks in the middle of the day — which happens to coincide with peak generation. That is favourable: the pump can run directly from PV during the day with the battery covering only starts and any evening running.

Pump energy (kWh/day) = pump power (kW) × hours of running

A 1.5 kW pump running 4 hours uses 6 kWh. At 5 peak-sun hours, that is 1.2 kW of array before losses, or around 1.5–1.6 kWp after derating. But PV output must also cover the surge — the inverter draws the start-up current from PV and battery together, so the battery must be sized to supply the difference briefly.

Practical installation notes

Note on certification

The HE310-5000-F holds CE EMC certification (CKEYS251201016) and GB 4943.1-2022 safety coverage (BDL260706S002), but no FCC or RoHS file. Battery type for this model is AGM deep-cycle or GEL, not lithium. Confirm before specifying — see the certifications page.