HE200-7200-FP — Paralleled Hybrid Inverter, up to 58.5 kW
One line: Scale to 58.5 kW by paralleling nine units, with three-phase output, generator auto-start and cloud monitoring.


Specifications
| Category | Item | Value |
|---|---|---|
| Inverter output | Maximum output power | 58500 W (9 units, expanded) / 58500 W (9 units, split-phase) |
| Maximum output voltage | 240 Vac ±5% (single phase) / 415 Vac ±5% (three phase) | |
| Maximum output current | 265.9 A (single phase) / 153.95 A (three phase) | |
| Output frequency | 50/60 Hz | |
| Output waveform | Pure sine wave | |
| Output topology | L1+N1+L2+N2+PE | |
| Max parallel units | 9 | |
| Battery | Battery type | AGM / lithium |
| Rated battery voltage | 48 Vdc | |
| Max combined PV charge current | 120 A | |
| PV input | MPPT strings | 1 per unit, 9 across 9 units |
| Maximum input power | 9000 W per string | |
| Maximum open-circuit voltage | 500 Vdc | |
| Maximum short-circuit current | 27 A | |
| Open-circuit working range | 60–450 Vdc | |
| Max PV charge efficiency | 99.5% | |
| Grid / generator input | Input voltage range | 90–280 Vac |
| Rated input voltage | 220 Vac | |
| Input frequency | 50/60 Hz | |
| Maximum current | 40 A | |
| General | Dimensions | 397 × 332 × 118 mm |
| Packing dimensions | 478 × 410 × 205 mm | |
| Net weight | 8.7 kg | |
| Gross weight | 9.8 kg | |
| Protection rating | IP21 | |
| Operating temperature | −10 to 60 °C | |
| Cooling | Smart fan cooling | |
| Humidity | 5–95% |
Features unique to this model
- Generator auto-start — the unit can start a connected generator automatically.
- RS232 communication plus Wi-Fi.
- External Wi-Fi module — app and cloud platform showing generation data, fault alarms, with OTA firmware updates.
- 9-unit parallel — single-phase expansion or three-phase (415 Vac) output.


How parallel expansion works
Each unit carries its own MPPT string (up to 9000 W), so nine units accept up to nine PV strings. Battery, output and control are interconnected. The system presents to the load as a single supply — 240 Vac single-phase, or 415 Vac three-phase.
Planning implications:
- Battery bank scales with the system, not the unit. Nine units charging at up to 120 A each is a very large combined charge current. The battery bank must be sized so the combined charge current stays within the chemistry's 0.2C (lead-acid) or 0.5C (lithium) limit. This is the single most common sizing error on parallel systems.
- Cable and protection are system-level. Three-phase output at 153.95 A per phase and single-phase at 265.9 A require appropriately rated switchgear.
- Start with the load. Decide the target output (say 40 kW), divide by the single-unit class, then confirm the battery and PV support that many units.
Typical applications
- Commercial and light-industrial sites needing three-phase supply with backup.
- Rural electrification where a 415 Vac three-phase network is required.
- Larger agricultural installations with multiple pumps and motors.
- Sites with a standby generator where auto-start removes manual intervention.
Connections, monitoring and accessories
Terminal layout, system wiring, monitoring options and the accessories supplied with the unit.



Certification coverage
| Certification | Status |
|---|---|
| CE (LVD + EMC) — M.2025.206.C116069 | Covered (listed model) |
| FCC SDoC — CKEYS251013025 | Covered (series) |
| RoHS 2.0 — CKEYS251013024 | Covered (series) |
| GB 4943.1-2022 — RKEYS250917157 | Covered (series) |
Note: CE coverage is for the HE200-7200-FP model as listed on the UDEM certificate. Confirm the exact parallel configuration and any IP54 variant before quoting certification. Full detail on the certifications page.
Related models
- Single-unit equivalent: HE200-7200-F — 6200 W
- Larger parallel system: HE300-12000-FP — 99 kW across 9 units
- Hybrid inverter range